- Power Distribution Equipment[1]
- Control Cables[5]
- Electrical Wires[10]
- Other Wires[1]
- Power Cables[10]
- Cable Sleeves[1]
- Aluminum Bars[1]
- Steel Wire[1]
- Contact Person : Mr. D Harry
- Company Name : Henan Qunxin Industrial Co., Ltd.
- Tel : 86-0371-86087788
- Fax : 86-0371-86159988
- Address : Henan,Gongyi City,No.288 Wenchang Road, Nanluo Village, Huiguo Town,Gongyi City,Henan Province
- Country/Region : China
- Zip : 451283
Related Product Searches:Aerial Bunched Cable manufactor,High Quality,abc cables, ABC cable manufacturers,ABC cable
Applications:
Used to supply 3 phase power, usually from a pole- mounted transformer, to the user's service head where connect to the service entrance cable. To be used at voltages of 600 volts or less phase to phase and at conductor temperatures not to exceed 75°C for PE insulated Conductors or 90°C for crosslinked polyethylene (XLPE) insulated conductors.
Construction:Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC, or ACSR. One conductor is manufactured with an extruded ridge for phase identification.
Installation:For service at 600 volts or less (phase to phase) at a maximum conductor temperature of 75ºC for Polyethylene insulation or 90ºC for Cross-Linked (XLPE) insulation
SpecificationsQuadruplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.B-230 Aluminum Wire, 1350-H19 for electrical purposesB-231 Aluminum Conductors, concentric-lay-strandedB-232 Aluminum Conductors, concentric-lay-stranded, coated steel reinforced(ACSR)B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors.B-498 Zinc-coated Steel Core Wire for Aluminum Conductors, steel reinforced(ACSR/AZ)
Triplex Service Drop cable meets or exceeds all aplicable requierements of ANSI/ICEA S-76-474. Remarks:1) Designated sizes are : ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTMB-399 for 6201.2) Conductor temperature of 90°C for XLPE 75°C for PE; ambient temperatures of 40°C; emissivity 0.9; 2ft./sec/wind in sun.
All of our products can be manufactured in accordance with international standards such as IEC, ASTM, BS, DIN/VDE, JIS, NF, CSA, AS/NZS and ect.
1.Application | |||||||||||
Primarily used for 120volt overhead service application such as street lighting,outdoor lighting,and temporary service for construction.To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 75 for polyethylene insulated conductors or 90 for crosslinked polyethylene(XLP) insulated conductors. | |||||||||||
2.Construction | |||||||||||
Code*Word | Phase conductor | Bare Neutral Message | Nominal lay Length | Weight Per | Allo wable Amp acitles | ||||||
1000 ft.(lbs.) | |||||||||||
Size | Stranding | Insul | Size | Stranding | Rated | inches | XLP | POLY | XLP | POLY | |
(A WG) | Thick(Mils) | (AWG) | Strength | ||||||||
(lbs.) | |||||||||||
AAC Neutral-messenger | |||||||||||
Pekingese | 6 | 1 | 45 | 6 | 7 | 563 | 10.36 | 61 | 61 | 85 | 70 |
Collie | 6 | 7 | 45 | 6 | 7 | 563 | 10.36 | 64 | 64 | 85 | 70 |
Dachshund | 4 | 1 | 45 | 4 | 7 | 881 | 10.36 | 92 | 92 | 115 | 90 |
Spaniel | 4 | 7 | 45 | 4 | 7 | 881 | 10.36 | 96 | 96 | 115 | 90 |
Doberman | 2 | 7 | 45 | 2 | 7 | 1350 | 14.88 | 147 | 147 | 150 | 120 |
Malemute | 1/0 | 9 | 60 | 1/0 | 7 | 1990 | 14.88 | 234 | 234 | 205 | 160 |
*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP) | |||||||||||
+Conductor temperature of 90 for XLP,75 for Poly;ambient temperature of 40;emissivity 0.2;2ft./sec.Wind in sun. |
Aerial Bunched Cable manufactor